Serviceline Industrial Sensors
Serviceline Explosion Protection

Gateway for PROFINET FB8222B.1.EL

FB8222B.1.EL
  • Communication via PROFINET
  • Installation in suitable enclosures in Zone 1
  • Interface between the I/O modules and the PCS/PLC
  • Non-volatile memory for configuration and parameter settings
  • Permanently self-monitoring
  • MRP and S2 redundancy
  • HART communication via HART-IP
  • Shared Device und Dynamic Reconfiguration

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Utdrag ur datablad: Tekniska data för  FB8222B.1.EL

Product Description
Gateway for PROFINET
Supply
Connectionbackplane bus
Nominal voltage12 V DC , only in connection with the power supplies FB92**
Power dissipation4.24 W
Power consumption4.24 W
Fieldbus connection
Fieldbus typePROFINET
Ethernet Interface
Connection typeM12 , via front connector
Transfer rate10BASE-T, 100BASE-TX 100 MBit/s
Station connectiondirectly to PCS or PLC or via hubs or switches
Cable typeSFTP in accordance with ISO/IEC 11801 for Cat 5e or better
Bus lengthmax. 100 m per link
AddressingDHCP or fixed IP address
Ethernet addressIP V4 address (factory standard setting: 0.0.0.0, auto IP, DHCP)
Supported I/O modulesFB1x01*…FB1x03*, FB1x08*, FB1x09*, FB2x01*...FB2x17*, FB3x01*…FB3x06*, FB4x01*, FB4x02*, FB4x04*…FB4x06*, FB5x01*, FB5x02*, FB5x04*…FB5x06*, FB6x01*, FB6x05*, FB6x06*, FB6x08*, FB6x10*…FB6x17*, FB7x04
PROFINET conformance classCC B
Internal bus
Connectionbackplane bus
Galvanic isolation
Ethernet/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 32 V DC (SELV/PELV)
RS 485 interface/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V DC
Insulation voltage1500 V AC acc. to IEEE 802.3u
Electrical isolation
Power supply, internal bus/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 30 V DC
Indicators/settings
LED indicationSee below in the front view
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-78
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionvia backplane
Massapprox. 965 g
Dimensions57 x 107 x 151 mm
Data for application in connection with hazardous areas
EU-type examination certificatePTB 19 ATEX 2007 U
MarkingEx-Hexagon II 2G Ex db eb ib q IIC Gb
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018
EN 60079-1:2014
EN 60079-5:2015
EN 60079-7:2015
EN 60079-11:2012
International approvals
ATEX approval
ATEX certificatePTB 19 ATEX 2007 U
IECEx approval
IECEx certificateIECEx PTB 19.0025U
IECEx markingEx db eb ib q IIC Gb
General information
System informationThe module may be installed only in the associated backplanes FB9262BP*.2 in Zone 1, Zone 2, or outside the hazardous area. Observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: FB8222B.1.EL

Datasheet: FB8222B.1.EL

DatasheetFile TypeFile Size
Datasheet FB8222B.1.ELPDF1111 KB
Datenblatt FB8222B.1.ELPDF1115 KB

Documents: FB8222B.1.EL

ManualsFile TypeFile Size
CFC for STEP 7PDF1447 KB
Configuration instructions STEP 7PDF3870 KB
Configuration instructions TIA PortalPDF4041 KB
FB Hardware ManualPDF9157 KB
ManualPDF5915 KB
CFC für STEP 7PDF1472 KB
FB-Hardware-HandbuchPDF9182 KB
HandbuchPDF6011 KB
Konfigurationsanleitung STEP 7PDF3894 KB
Konfigurationsanleitung TIA PortalPDF4061 KB
Instruction manuals
ИнструкцииPDF172 KB
Návod k poużitíPDF165 KB
Instruktions manualPDF164 KB
Instruction manualPDF169 KB
KasutusjuhendPDF160 KB
KäyttöohjePDF160 KB
Manuel d'instructionsPDF167 KB
BetriebsanleitungPDF171 KB
Οδηγίες χρήσηςPDF175 KB
HandleidingPDF165 KB
Instruction manual / BetriebsanleitungPDF164 KB
Használati útmutatóPDF167 KB
Manuale di istruzioniPDF165 KB
Lietošanas pamācībaPDF164 KB
Instrukciju vadovasPDF165 KB
Instrukcja obsługiPDF167 KB
Manual de instruçõesPDF166 KB
Manual de utilizarePDF166 KB
Návod na poużitiePDF166 KB
Navodila za uporaboPDF163 KB
Manual de instruccionesPDF167 KB
ManualPDF162 KB
Application reports
Application Report - Communication Redundancy for Uninterrupted OperationPDF529 KB
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field DevicesPDF208 KB
Application Report - Space Saving Extension for Existing PlantsPDF300 KB
Application Report - Using Remote I/O Systems for the Efficient Digitalization of PlantsPDF371 KB
Applikationsbericht - Platzsparende Erweiterung für bestehende AnlagenPDF300 KB
Applikationsbericht - Redundanz der Kommunikation für ungestörten BetriebPDF530 KB
Applikationsbericht - Remote-I/O-Systeme Typ LB und FB für digitale Anbindung analoger FeldgerätePDF208 KB
Applikationsbericht - Remote-I/O-Systeme für effiziente AnlagendigitalisierungPDF365 KB
Documents
Software Product Note Remote I/O DTM / Softwareproduktschein Remote I/O DTMPDF256 KB
Release NotePDF383 KB

CAD+CAE: FB8222B.1.EL

CADFile TypeFile Size
CAD 3-D / CAD 3-DSTP7774 KB
CAD Portal / CAD PortalLINK---
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
EPLAN macro EDZ / EPLAN Makro EDZEDZ1095 KB